Sustainability is an international, open-access, peer-reviewed journal focused on all aspects of sustainability—environmental, social, economic, technical, and cultural. Publishing semimonthly, it welcomes research from natural and applied sciences, engineering, social sciences, and humanities, encouraging detailed experimental and methodological r...

Genetic Algorithm-Optimized Adaptive Network Fuzzy Inference System-Based VSG...

Author(s):

Mohd Hanif Othman
Department of Electrical Engineering, Faculty of Engineering, University of Malaya (UM), Kuala Lumpur 50603, Malaysia
Hazlie Mokhlis
Department of Electrical Engineering, Faculty of Engineering, University of Malaya (UM), Kuala Lumpur 50603, Malaysia
Marizan Mubin
Department of Electrical Engineering, Faculty of Engineering, University of Malaya (UM), Kuala Lumpur 50603, Malaysia
Nur Fadilah Ab Aziz
Department of Electrical and Electronic Engineering, University Tenaga Nasional (UNITEN), Jalan Ikram-UNITEN, Kajang 43000, Malaysia
Hasmaini Mohamad
School of Electrical Engineering, College of Engineering, University Teknologi MARA (UITM), Shah Alam 40450, Malaysia
Shameem Ahmad
Department of Electrical Engineering, Faculty of Engineering, University of Malaya (UM), Kuala Lumpur 50603, Malaysia
Nurulafiqah Nadzirah Mansor
Department of Electrical Engineering, Faculty of Engineering, University of Malaya (UM), Kuala Lumpur 50603, Malaysia


Download the PDF file of the original publication


Year: 2022 | Doi: 10.3390/su141710798

Copyright (license): Creative Commons Attribution 4.0 International (CC BY 4.0) license.


[Full title: Genetic Algorithm-Optimized Adaptive Network Fuzzy Inference System-Based VSG Controller for Sustainable Operation of Distribution System]

[[[ p. 1 ]]]

[Summary: This page is the article's citation and copyright information. It introduces the authors, their affiliations, and the abstract. The abstract highlights the use of a GA-ANFIS controller to improve VSG performance in renewable energy based distribution systems for frequency stability.]

Citation: Othman, M.H.; Mokhlis, H.; Mubin, M.; Ab Aziz, N.F.; Mohamad, H.; Ahmad, S.; Mansor, N.N. Genetic Algorithm-Optimized Adaptive Network Fuzzy Inference System- Based VSG Controller for Sustainable Operation of Distribution System Sustainability 2022 , 14 , 10798 https://doi.org/10.3390/su 141710798 Academic Editor: Alberto-Jesus Perea-Moreno Received: 30 June 2022 Accepted: 23 August 2022 Published: 30 August 2022 Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations Copyright: © 2022 by the authors Licensee MDPI, Basel, Switzerland This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/) sustainability Article Genetic Algorithm-Optimized Adaptive Network Fuzzy Inference System-Based VSG Controller for Sustainable Operation of Distribution System Mohd Hanif Othman 1 , Hazlie Mokhlis 1, * , Marizan Mubin 1 , Nur Fadilah Ab Aziz 2 , Hasmaini Mohamad 3 , Shameem Ahmad 1,4 and Nurulafiqah Nadzirah Mansor 1 1 Department of Electrical Engineering, Faculty of Engineering, University of Malaya (UM), Kuala Lumpur 50603, Malaysia 2 Department of Electrical and Electronic Engineering, University Tenaga Nasional (UNITEN), Jalan Ikram-UNITEN, Kajang 43000, Malaysia 3 School of Electrical Engineering, College of Engineering, University Teknologi MARA (UITM), Shah Alam 40450, Malaysia 4 Department of Electrical and Electronic Engineering, Faculty of Engineering, American International University—Bangladesh (AIUB), Dhaka 1229, Bangladesh * Correspondence: hazli@um.edu.my Abstract: To achieve a more sustainable supply of electricity and reduce dependency on fuels, the application of renewable energy sources-based distribution systems (DS) is stimulating. However, the intermittent nature of renewable sources reduces the overall inertia of the power system, which in turn seriously affects the frequency stability of the power system. A virtual synchronous generator can provide inertial response support to a DS. However, existing active power controllers of VSG are not optimized to react to the variation of frequency changes in the power system. Hence this paper introduces a new controller by incorporating GA-ANFIS in the active power controller to improve the performance of the VSG. The advantage of the proposed ANFIS-based controller is its ability to optimize the membership function in order to provide a better range and accuracy for the VSG responses. Rate of change of frequency (ROCOF) and change in frequency are used as the inputs of the proposed controller to control the values of two swing equation parameters, inertia constant (J) and damping constant (D). Two objective functions are used to optimize the membership function in the ANFIS. Transient simulation is carried out in PSCAD/EMTDC to validate the performance of the controller. For all the scenarios, VSG with GA-ANFIS (VOFIS) managed to maintain the DS frequency within the safe operating limit. A comparison between three other controllers proved that the proposed VSG controller is better than the other controller, with a transient response of 22% faster compared to the other controllers Keywords: virtual synchronous generator; active power controller; inertial frequency response 1. Introduction The desire to “Go Green”due to worries about the shrinking non-renewable energy sources and the preservation of the environment has substantially increased the use of renewable energy sources (RES) for electric power generation. In addition, to be in line with United Nations Sustainable Development Goal (SDG) and ensure access to affordable, reliable, sustainable, and modern energy for all, the use of RES is increasing [ 1 ]. In this regard, most countries have set a target to achieve a renewable energy mix in their total generation by 2030, which has resulted in an increase in the level of distributed generation (DG). For instance, Malaysia has given the regulations to realize a 31% objective from the entire share of energy from RES [ 2 ] by 2025. DG has been the impetus in the transformation of the traditional distribution scheme to a much more green, sustainable, flexible, reliable, Sustainability 2022 , 14 , 10798. https://doi.org/10.3390/su 141710798 https://www.mdpi.com/journal/sustainability

[[[ p. 2 ]]]

[Summary: This page discusses the increasing use of distributed systems (DS) with renewable energy sources (RES). It highlights the inertia problem in DS and introduces VSG as a solution. It then discusses the limitations of existing VSG controllers and the need for improvement.]

Sustainability 2022 , 14 , 10798 2 of 16 and efficient power distribution scheme known as distributed system (DS). The introduction of DS into the power system helps to promote the usage of RES. Furthermore, power losses in the system could be reduced with power generation closer to the load points. Moreover, DS can reduce peak power generation from the centralized coal-fired power plant. Thus, reducing the emission of greenhouse gases Nevertheless, DS has many issues that need to be addressed pertaining to their voltage and frequency standard [ 3 ], especially during islanding. For DS to be independent of the main grid, it needs to solve the lack of power inertia problem in its power system [ 4 ]. The main sources of power generation in a DS come from solar power, small wind turbines, a battery energy storage system, and mini hydro power, all of which have little to no inertia reserve. During islanding, DS based on RES could not react to any sudden changes during the inertial period of frequency responses. DS-based RESs are connected to the power system via a power converter that does not offer inertia support like a conventional synchronous generator (SG). Even the process of (sudden) islanding for a low inertia DS would cause spikes in frequency and risk damaging critical equipment in the DSs. One way to maintain the stability of the DS is to introduce ancillary service that can inject artificial inertia into the network A few solutions were introduced to mitigate low inertia power systems, namely virtual synchronous generator (VSG). VSG is a concept that modeled a cylindrical-rotor-type SG architecture. It was first proposed in the European project “VSYNC” [ 3 ]. The swing equation in SG is used to calculate the VSG inertial response. In an SG, these parameters are determined by the rotational kinetic energy stored in the rotor at a certain rated speed These parameters cannot be changed unless one changes the physical component of the rotor. However, in a VSG controller, these parameters are not constrained to any physical limitation. Therefore, they can be adjusted in real-time to improve and optimize the controller performance. A variety of VSG controller methods have been reviewed, ranging from conventional to intelligence techniques [ 5 ]. Initially, VSG used a droop controller to regulate the inertia response [ 6 ]. An improved droop controller was introduced, which helped to reduce the frequency nadir, but the droop controller alone could not solve the oscillation problem that occurs after each VSG injection Alternating methods were proposed to improve the dynamic performance of VSG inertial response. Large inertia is needed to overcome the high rate of change of frequency (ROCOF), while low inertia is needed to subdue the oscillation. By adjusting the key parameters in the VSG controller, the oscillation problem is reduced. Thus, VSG with an alternating moment of inertia was introduced to compensate for the problem from the droop controller by damping the power oscillation after each VSG response. However, the proposed technique switched between small and big virtual inertia value [ 7 ], which limit the range of the VSG inertia support. Another concept to mitigate the power oscillation problem is by alternating the damping constant of the VSG controller. However, it does not reduce the frequency of nadir during high ROCOF [ 8 ]. The time for the frequency to recover to its nominal frequency is too long. Although it helps reduce the oscillation, it takes a longer time to stabilize and return to nominal frequency. Consequently, the addition of a fuzzy inference system (FIS) in the VSG controller was proposed to regulate the alternating value of inertia. A variety of FIS techniques have been used to improve the VSG concept FIS in [ 9 ] regulated the VSG output only from the ROCOF value. With a fixed range of membership functions (MF), the FIS proposed was unable to cover a wide range of overand under-frequency events. In [ 10 ], optimization of FIS was applied to regulate only the oscillation of VSG injection. In contrast, FIS in [ 11 ] was used to generate active and reactive power references for VSG according to the DS connection mode. However, the FIS design had too many inputs and the input MF were not optimized, resulting limited VSG range response There is no work being carried out to optimize the membership function of a fuzzy inference system (FIS) for the active power controller in VSG. Either the input MF or the output MF. By optimizing both the input and output MF, a wide range of responses and

[[[ p. 3 ]]]

[Summary: This page introduces a new controller incorporating GA-ANFIS to improve VSG active power control by optimizing inertia (J) and damping (D) constants. It outlines the paper's contributions: a new VSG active power injection method and real-time scheduling of J and D values.]

Sustainability 2022 , 14 , 10798 3 of 16 input scenarios could be managed in real-time by scheduling through FIS. FIS will optimize and update the MF whenever the system responses are out of the safe operating region. Instead of continuous MF optimization, most controllers change the values of J and D in a linear or flip-flop manner Considering the limitations of the previous VSG controllers, this paper proposes a new controller, which incorporates a genetic algorithm (GA) optimized adaptive network-based fuzzy inference system (ANFIS) to improve the performance of the active power controller in VSG. Two parameters of VSG’s swing equation, namely inertia constant, J , and damping constant, D , are optimized to give a wide range of VSG responses. The input parameters for ANFIS are the rate of change of frequency (ROCOF) and the change in frequency. While the output parameters for ANFIS are inertia constant, J, and damping constant, D. Membership function (MF) used for both the input and output are gauss MF. GA is used to optimize the MF for both the input and output of ANFIS. As a result, both input and output MF are heuristically designed to manage a wide range of interruptions and responses Optimization of the ANFIS using GA has given the controller an optimized range of inertial responses based on real-world simulation. This concept improves both the transient and the oscillation damping of the inertial response of the VSG, which ensures the sustainable and reliable operation of the RES-based DS. The performance of the proposed VSG controller is verified on an 11 kV, 22 bus Malaysian distribution system consisting of two mini hydro and one solar farm. Further, a comparative study has been conducted between the optimized and non-optimized VSG controllers presented to prove the superiority of the proposed controller. The main contribution of this paper is as follows: • Proposed a new way of VSG active power injection through optimizing both the input and output MF of ANFIS • Through the optimizations, real-time scheduling of values J and D is produced. It managed to cover a wide range of interruptions and able to give appropriate active power responses The rest of the paper is arranged as follows. Section 2 is the methodology for the controller and test system used, Section 3 is the verification of the controller effectiveness by simulation using PSCAD EMTDC, and finally, Section 4 concludes the findings of the paper 2. Optimized Adaptive Network-Based Fuzzy Inference System Using Genetic Algorithm 2.1. VSG Active Power Controller The common topology of VSG consists of three major components: the inverter, controller, and energy storage system, as shown in Figure 1 . The well-known swing Equation (1) is used as the basic component for the VSG controller P in − P out = J ω o ω m dt + D ∆ ω (1) where P in , P out , J , ω o , and D are the input power (similar to prime mover power in an SG), the output power of the VSG, the moment of inertia of the virtual rotor, the virtual velocity of the virtual rotor, and the damping factor, respectively ∆ ω is the difference between the grid frequency and the reference frequency. Figure 2 shows the active power control structure for a VSG. The controller mimics the ability of an SG by using the swing equation in (1). In this paper, a similar approach to VSYNC is applied, where the frequency changes are used as the input reference. In VSYNC, the phase-locked loop is designed to produce the changes in frequency and ROCOF. Both of these parameters are vital to the GA-ANFIS design. In VSYNCH, the inertial power is calculated linearly as in Equation (2), where ∆ ω is the change in frequency and d ∆ ω dt is the ROCOF. GA-ANFIS is inspired by the controller method used in VSYNCH and the traditional swing equation. Frequency and ROCOF are used as the input to the GA-ANFIS. As shown in Figure 3 , both inputs will affect the value

[[[ p. 4 ]]]

[Summary: This page shows a UML diagram for the proposed GA-ANFIS controller. It shows active power control structure for VSG and a modified VSG with GA-ANFIS controller.]

Sustainability 2022 , 14 , 10798 4 of 16 of inertia constant, J , and damping constant, D , subsequently help the VSG injects and absorbs the right amount of active power into the power system P inertia = K SOC ∆ SOC + K p ∆ ω + K i d ∆ ω dt (2) Sustainability 2022 , 14 , x FOR PEER REVIEW 4 of 16 inspired by the controller method used in VSYNCH and the traditional swing equation. Frequency and ROCOF are used as the input to the GA-ANFIS. As shown in Figure 3, both inputs will affect the value of inertia constant, J, and damping constant, D , subsequently help the VSG injects and absorbs the right amount of active power into the power system. {?} = {?} ∆{?}{?}{?} + {?} ∆{?} + {?} {?}∆{?} {?}{?} (2) Virtual Synchronous Generator Active Power Controller GA-ANFIS OPIMIZATION J D ROCOF Frequency change Active Power Injection Distribution System (Power Grid) ENERGY STORAGE SYSTEM Inverter Figure 1. UML diagram for the proposed GA-ANFIS controller. f vsg - + J 2 s f g GOVERNER P VSG 3 EU sinδ X 1 s + - - D Figure 2. Active power controller for VSG. f vsg - + J 2 s f g GOVERNER P VSG 3 EU sinδ X 1 s + - - D 1 s GA-ANFIS ∆f d∆f/dt J Anfis D Anfis Figure 3. Modified VSG with GA-ANFIS controller. 2.2. Adaptive Network Fuzzy Inference System The evolutionary adaptive neuro-fuzzy inference system (ANFIS) is a kind of artificial neural network that is based on the Takagi-Sugeno fuzzy inference system (FIS). This technique was developed in 1990. It has five layers of a fuzzy inference system. ANFIS used a data set of inputs and outputs to create the rules and membership function. In this paper, as shown in Figures 4 and 5, the ANFIS structure has two inputs and two outputs. It is composed of six membership functions and six rules. Figure 1. UML diagram for the proposed GA-ANFIS controller Sustainability 2022 , 14 , x FOR PEER REVIEW 4 of 16 inspired by the controller method used in VSYNCH and the traditional swing equation. Frequency and ROCOF are used as the input to the GA-ANFIS. As shown in Figure 3, both inputs will affect the value of inertia constant, J, and damping constant, D , subsequently help the VSG injects and absorbs the right amount of active power into the power system. {?} = {?} ∆{?}{?}{?} + {?} ∆{?} + {?} {?}∆{?} {?}{?} (2) Virtual Synchronous Generator Active Power Controller GA-ANFIS OPIMIZATION J D ROCOF Frequency change Active Power Injection Distribution System (Power Grid) ENERGY STORAGE SYSTEM Inverter Figure 1. UML diagram for the proposed GA-ANFIS controller. f vsg - + J 2 s f g GOVERNER P VSG 3 EU sinδ X 1 s + - - D Figure 2. Active power controller for VSG. f vsg - + J 2 s f g GOVERNER P VSG 3 EU sinδ X 1 s + - - D 1 s GA-ANFIS ∆f d∆f/dt J Anfis D Anfis Figure 3. Modified VSG with GA-ANFIS controller. 2.2. Adaptive Network Fuzzy Inference System The evolutionary adaptive neuro-fuzzy inference system (ANFIS) is a kind of artificial neural network that is based on the Takagi-Sugeno fuzzy inference system (FIS). This technique was developed in 1990. It has five layers of a fuzzy inference system. ANFIS used a data set of inputs and outputs to create the rules and membership function. In this paper, as shown in Figures 4 and 5, the ANFIS structure has two inputs and two outputs. It is composed of six membership functions and six rules. Figure 2. Active power controller for VSG Sustainability 2022 , 14 , x FOR PEER REVIEW 4 of 16 inspired by the controller method used in VSYNCH and the traditional swing equation. Frequency and ROCOF are used as the input to the GA-ANFIS. As shown in Figure 3, both inputs will affect the value of inertia constant, J, and damping constant, D , subsequently help the VSG injects and absorbs the right amount of active power into the power system. {?} = {?} ∆{?}{?}{?} + {?} ∆{?} + {?} {?}∆{?} {?}{?} (2) Virtual Synchronous Generator Active Power Controller GA-ANFIS OPIMIZATION J D ROCOF Frequency change Active Power Injection Distribution System (Power Grid) ENERGY STORAGE SYSTEM Inverter Figure 1. UML diagram for the proposed GA-ANFIS controller. f vsg - + J 2 s f g GOVERNER P VSG 3 EU sinδ X 1 s + - - D Figure 2. Active power controller for VSG. f vsg - + J 2 s f g GOVERNER P VSG 3 EU sinδ X 1 s + - - D 1 s GA-ANFIS ∆f d∆f/dt J Anfis D Anfis Figure 3. Modified VSG with GA-ANFIS controller. 2.2. Adaptive Network Fuzzy Inference System The evolutionary adaptive neuro-fuzzy inference system (ANFIS) is a kind of artificial neural network that is based on the Takagi-Sugeno fuzzy inference system (FIS). This technique was developed in 1990. It has five layers of a fuzzy inference system. ANFIS used a data set of inputs and outputs to create the rules and membership function. In this paper, as shown in Figures 4 and 5, the ANFIS structure has two inputs and two outputs. It is composed of six membership functions and six rules. Figure 3. Modified VSG with GA-ANFIS controller 2.2. Adaptive Network Fuzzy Inference System The evolutionary adaptive neuro-fuzzy inference system (ANFIS) is a kind of artificial neural network that is based on the Takagi-Sugeno fuzzy inference system (FIS). This technique was developed in 1990. It has five layers of a fuzzy inference system. ANFIS used a data set of inputs and outputs to create the rules and membership function. In this paper, as shown in Figures 4 and 5 , the ANFIS structure has two inputs and two outputs. It is composed of six membership functions and six rules.

[[[ p. 5 ]]]

[Summary: This page shows a basic architecture of the proposed ANFIS controller and five layers of ANFIS structure. It describes the first layer of ANFIS: the fuzzification layer. It uses MF to obtain fuzzy clusters from the input data set.]

Sustainability 2022 , 14 , 10798 5 of 16 Sustainability 2022 , 14 , x FOR PEER REVIEW 5 of 16 Frequency Drop GA-ANFIS Rate of Change of Frequency Inertia Constant, J Damping Constant, D Figure 4. Basic architecture of the proposed ANFIS controller. ∆f d∆f/dt A 1 Ai B 1 Bj w 1 w 2 w 3 wi f 1 i f 1 i f 2 i f 2 i J D w 1 w 2 w 3 wi ∑ 2 ∑ 1 LAYER 1 LAYER 2 LAYER 3 LAYER 4 LAYER 5 Figure 5. Five layers of ANFIS structure. The first layer is the fuzzification layer. It uses MF to obtain fuzzy clusters from the input data set. { a , b } is the premise parameters that shape the Gauss membership function (GMF) For this work, GMF is selected. It is selected for the simplicity of the MF equation, where it depends on two parameters, which represent the center and the width. GMF is also the basis for the connection between the fuzzy system and radial basis function neural networks. uA i and uB j , are the membership degrees of the linguistic label, A and B, as given in Equations (3) and (5). For this ANFIS design, I is set to 7 because each linguistic label has seven MF. {?}{?} ({?}) = {?}{?}{?}{?}{?}{?}{?}({?}, {?}) = {?} ( ) (3) {?} = {?}{?} ({?}) (4) {?}{?} ({?}) = {?}{?}{?}{?}{?}{?}{?}({?}, {?}) = {?} ( ) (5) {?} = {?}{?} ({?}) (6) The second layer is called the rule layer. Firing strengths, w i , of each rule are generated by using membership degrees in layer 1. Wi values are calculated as the following. {?} = {?} = {?}{?} ({?}). {?}{?} ({?}) {?} = 1,2 (7) The third layer is called the normalization layer. Normalized firing strength to each rule is calculated. The normalized value is the ratio of the firing strength, w i to the total of all firing strengths as given in Equation (8). Figure 4. Basic architecture of the proposed ANFIS controller Sustainability 2022 , 14 , x FOR PEER REVIEW 5 of 16 Frequency Drop GA-ANFIS Rate of Change of Frequency Inertia Constant, J Damping Constant, D Figure 4. Basic architecture of the proposed ANFIS controller. ∆f d∆f/dt A 1 Ai B 1 Bj w 1 w 2 w 3 wi f 1 i f 1 i f 2 i f 2 i J D w 1 w 2 w 3 wi ∑ 2 ∑ 1 LAYER 1 LAYER 2 LAYER 3 LAYER 4 LAYER 5 Figure 5. Five layers of ANFIS structure. The first layer is the fuzzification layer. It uses MF to obtain fuzzy clusters from the input data set. { a , b } is the premise parameters that shape the Gauss membership function (GMF) For this work, GMF is selected. It is selected for the simplicity of the MF equation, where it depends on two parameters, which represent the center and the width. GMF is also the basis for the connection between the fuzzy system and radial basis function neural networks. uA i and uB j , are the membership degrees of the linguistic label, A and B, as given in Equations (3) and (5). For this ANFIS design, I is set to 7 because each linguistic label has seven MF. {?}{?} ({?}) = {?}{?}{?}{?}{?}{?}{?}({?}, {?}) = {?} ( ) (3) {?} = {?}{?} ({?}) (4) {?}{?} ({?}) = {?}{?}{?}{?}{?}{?}{?}({?}, {?}) = {?} ( ) (5) {?} = {?}{?} ({?}) (6) The second layer is called the rule layer. Firing strengths, w i , of each rule are generated by using membership degrees in layer 1. Wi values are calculated as the following. {?} = {?} = {?}{?} ({?}). {?}{?} ({?}) {?} = 1,2 (7) The third layer is called the normalization layer. Normalized firing strength to each rule is calculated. The normalized value is the ratio of the firing strength, w i to the total of all firing strengths as given in Equation (8). Figure 5. Five layers of ANFIS structure The first layer is the fuzzification layer. It uses MF to obtain fuzzy clusters from the input data set. { a , b } is the premise parameters that shape the Gauss membership function (GMF). For this work, GMF is selected. It is selected for the simplicity of the MF equation, where it depends on two parameters, which represent the center and the width. GMF is also the basis for the connection between the fuzzy system and radial basis function neural networks uA i and uB j , are the membership degrees of the linguistic label, A and B, as given in Equations (3) and (5). For this ANFIS design, I is set to 7 because each linguistic label has seven MF µ A i ( x ) = gaussm f ( a , b ) = e − 1 2 ( x − a b ) 2 (3) O 1 i = µ A i ( x ) (4) µ B i ( x ) = gaussm f ( a , b ) = e − 1 2 ( x − a b ) 2 (5) O 2 i = µ B i ( x ) (6) The second layer is called the rule layer. Firing strengths, w i , of each rule are generated by using membership degrees in layer 1 w i values are calculated as the following O 2 i = w i = µ A i ( x ) · µ B i ( y ) i = 1, 2 (7)

[[[ p. 6 ]]]

[Summary: This page describes layers 3-5 of the ANFIS structure, including normalization, defuzzification, and summation. It also explains the genetic algorithm (GA) optimization process, where MF are optimized and tested in a Simulink model to improve VSG response accuracy.]

Sustainability 2022 , 14 , 10798 6 of 16 The third layer is called the normalization layer. Normalized firing strength to each rule is calculated. The normalized value is the ratio of the firing strength, w i to the total of all firing strengths as given in Equation (8) O 3 i = w i = w i w 1 + w 2 + w 3 + w 4 i ∈ { 1, 2, 3, 4 } (8) The fourth layer is the defuzzification layer. Weighted values of rules are calculated in each node shown in Equation (9). { p , q , r } is the parameter set. These are called the consequence parameters O 4 i = w i f ij = w ij p ij x + q ij y + r ij (9) The fifth layer is the summation. The output of the ANFIS is produced by summing the output obtained for each rule in the fuzzification layer O 5 i = ∑ i w i = ∑ i w i f i ∑ i w i (10) Initially, the membership function (MF) for the inputs and outputs are randomized within pre-set ranges. GA will sort the output and input values according to the data set. At every iteration, input MF and the output MF will be optimized, and a new fuzzy set is created. The new fuzzy set will be tested in the Simulink model, which is created to mimic the VSG response in the PSCAD simulation. At every iteration, an error from the Simulink model is produced and fed to the GA optimization to observe the accuracy of the fuzzy set 2.3. Genetic Algorithm Genetic algorithm (GA) is an optimization method that models the evolution process in nature. This optimization technique aims to achieve the best population by using the processes such as reproduction, crossover, and mutation. GA has been used in numerous problems in the fields [ 12 ]. In the case of GA-ANFIS, all parts of the ANFIS can be trained [ 13 ]. However, in this paper, multi-objective GA is used to optimize the gauss MF parameters { a , b } of ANFIS. The input MF and output MF parameters are set as the population cost. Figure 6 shows the flowchart of the implemented GA optimization to form the MF OF = Min { α 1 OF 1 + α 2 OF 2 } , where OF > 0; (11) OF 1 = Min {| f c − f i |} , f c = 60 Hz (12) OF 2 = 0.75 − ln x n x 0 ( 2 π n ) 2 + ln x n x 0 , n = 4 (13) The objective of GA optimization is to minimize the objective function (11) by accurately designing parameters of ANFIS input MF and output MF α 1 and α 2 are the normalization constants. Normalization by weighted sum is used to calculate α 1 and α 2 . It is normalized by the optimum value of each OF 1 and OF 2 α 1 = 1 OV 1 (14) α 2 = 1 OV 2 (15) where OV 1 and OV 2 is the optimum value for OF 1 and OF 2 . For this work, OV 1 is equal to 60, and OV 2 is equal to 0.75. Objective function 1 ( OF 1 ) in (12) is the frequency difference produced during each iteration f c is the reference frequency and f i is the maximum output frequency for each iteration OF 1 aims to minimize the frequency difference at every response. In contrast, objective function 2 ( OF 2 ) in (13) is the damping ratio calculation of

[[[ p. 7 ]]]

[Summary: This page details the genetic algorithm's objective function, aiming to minimize frequency difference and achieve optimal damping. It describes how the GA-ANFIS is used in PSCAD simulations and the GA-ANFIS rules surface generated from MATLAB.]

Sustainability 2022 , 14 , 10798 7 of 16 each response. The target for OF 2 is to obtain a response close to the optimal damping ratio, which is set at 0.75 x n is the peak response value at n period, x 0 is the peak response value for the first period. Once GA has optimized the ANFIS, GA-ANFIS will be used in the PSCAD simulation. A new data set from the PSCAD simulation will be used to improve the GA-ANFIS if the VSG response does not meet a certain minimum setpoint. A total of 70% of the PSCAD simulation data set is used as a training set, while 30% is used as a testing set. The number of iterations for GA optimization is set at 100 iterations. GA-ANFIS rules surface generated from MATLAB is shown in Figure 7 . Sustainability 2022 , 14 , x FOR PEER REVIEW 6 of 16 {?} = {?} = {?} {?} + {?} + {?} + {?} {?} ∈ {1,2,3,4} (8) The fourth layer is the defuzzification layer. Weighted values of rules are calculated in each node shown in Equation (9). { p , q , r } is the parameter set. These are called the consequence parameters. {?} = {?} {?} = {?} ({?} {?} + {?} {?} + {?} ) (9) The fifth layer is the summation. The output of the ANFIS is produced by summing the output obtained for each rule in the fuzzification layer. {?} = {?} = ∑ {?} {?} ∑ {?} (10) Initially, the membership function (MF) for the inputs and outputs are randomized within pre-set ranges. GA will sort the output and input values according to the data set. At every iteration, input MF and the output MF will be optimized, and a new fuzzy set is created. The new fuzzy set will be tested in the Simulink model, which is created to mimic the VSG response in the PSCAD simulation. At every iteration, an error from the Simulink model is produced and fed to the GA optimization to observe the accuracy of the fuzzy set. 2.3. Genetic Algorithm Genetic algorithm (GA) is an optimization method that models the evolution process in nature. This optimization technique aims to achieve the best population by using the processes such as reproduction, crossover, and mutation. GA has been used in numerous problems in the fields [12]. In the case of GA-ANFIS, all parts of the ANFIS can be trained [13]. However, in this paper, multi-objective GA is used to optimize the gauss MF parameters { a , b } of ANFIS. The input MF and output MF parameters are set as the population cost. Figure 6 shows the flowchart of the implemented GA optimization to form the MF. START GET DATA SET CREATE INITIAL ANFIS FROM DATA SET RANGE. RANDOMIZE ANFIS INITIATE GENETIC ALGORTIHM CONSTANT ITERATION =1000? SET NEW ANFIS BASED ON BEST PARAMETERS VALUE BEST OF? SETTING UP COST FUNCTION GET PARAMETERS INPUT MF, OUTPUTMF AS POPULATION COST CROSSOVER MUTATION UPDATE WORST AND BEST COST FUNCTION GLOBAL OF = BEST OF END YES NO YES NO Figure 6. GA-ANFIS flow chart. Figure 6. GA-ANFIS flow chart Sustainability 2022 , 14 , x FOR PEER REVIEW 7 of 16 {?}{?} = {?}{?}{?}{{?} {?}{?} + {?} {?}{?} } , {?}ℎ{?}{?}{?} {?}{?} 0; (11) {?}{?} = {?}{?}{?}{|{?} − {?} |} , {?} = 60 Hz (12) {?}{?} = 0.75 − {?}{?} {?} {?} (2{?}{?}) + {?}{?} {?}{?} , {?} = 4 (13) The objective of GA optimization is to minimize the objective function (11) by accurately designing parameters of ANFIS input MF and output MF. {?} and {?} are the normalization constants. Normalization by weighted sum is used to calculate {?} and {?} . It is normalized by the optimum value of each OF 1 and OF 2 . {?} 1 = 1 {?}{?} 1 (14) {?} 2 = 1 {?}{?} 2 (15) where OV 1 and OV 2 is the optimum value for OF 1 and OF 2 . For this work, OV 1 is equal to 60, and OV 2 is equal to 0.75. Objective function 1 (OF 1) in (12) is the frequency difference produced during each iteration. {?} is the reference frequency and {?} is the maximum output frequency for each iteration. OF 1 aims to minimize the frequency difference at every response. In contrast, objective function 2 (OF 2) in (13) is the damping ratio calculation of each response. The target for OF 2 is to obtain a response close to the optimal damping ratio, which is set at 0.75. {?} is the peak response value at n period, {?} is the peak response value for the first period. Once GA has optimized the ANFIS, GA-ANFIS will be used in the PSCAD simulation. A new data set from the PSCAD simulation will be used to improve the GA-ANFIS if the VSG response does not meet a certain minimum setpoint. A total of 70% of the PSCAD simulation data set is used as a training set, while 30% is used as a testing set. The number of iterations for GA optimization is set at 100 iterations. GA-ANFIS rules surface generated from MATLAB is shown in Figure 7. ( a ) ( b ) Figure 7. GAANFIS rules surface for ( a ) J , inertia constant, and ( b ) D , damping constant. 3. Test System Structure and Scale The proposed VSG controller is verified in PSCAD/EMTDC software, where GA-AN- FIS is first optimized in MATLAB/SIMULINK. An existing 11 kV Malaysian actual distribution network was used as the test system shown in Figure 8. The system consists of 21 lumped loads. The base load is provided by 2 mini hydro and a solar farm powering up the distribution system. The voltage of the mini hydro is stepped up using a 1 MVA, 3.3/11 kV transformer. DS is also connected to the main grid via a two-step-down 132/11 kV, 30 MVA transformer. Initially, from time 0 to 1.5 s, DS was connected to the main grid for Figure 7. GAANFIS rules surface for ( a ) J , inertia constant, and ( b ) D , damping constant.

[[[ p. 8 ]]]

[Summary: This page describes the test system: an 11 kV Malaysian distribution network simulated in PSCAD/EMTDC with GA-ANFIS optimized in MATLAB/SIMULINK. It details the system's components, including mini hydro, solar farm, VSGs, and their parameters.]

Sustainability 2022 , 14 , 10798 8 of 16 3. Test System Structure and Scale The proposed VSG controller is verified in PSCAD/EMTDC software, where GA- ANFIS is first optimized in MATLAB/SIMULINK. An existing 11 kV Malaysian actual distribution network was used as the test system shown in Figure 8 . The system consists of 21 lumped loads. The base load is provided by 2 mini hydro and a solar farm powering up the distribution system. The voltage of the mini hydro is stepped up using a 1 MVA, 3.3/11 kV transformer. DS is also connected to the main grid via a two-step-down 132/11 kV, 30 MVA transformer. Initially, from time 0 to 1.5 s, DS was connected to the main grid for the mini hydro initialization process. At time t = 1.5 s, DS was islanded. A total of 6 VSGs connected at buses 5, 6, 16, 18, 19, and bus 20. Each of the VSGs uses super magnetic energy storage (SMES) as the energy source. The PV farm is rated at 1.3 MW, connected at bus no 1. A dc-dc converter with maximum power point tracking and a voltage source converter is used to control the solar power. The parameters of the VSG-SME are listed in Tables 1 – 3 . Sustainability 2022 , 14 , x FOR PEER REVIEW 8 of 16 the mini hydro initialization process. At time t = 1.5 s, DS was islanded. A total of 6 VSGs connected at buses 5, 6, 16, 18, 19, and bus 20. Each of the VSGs uses super magnetic energy storage (SMES) as the energy source. The PV farm is rated at 1.3 MW, connected at bus no. 1. A dc-dc converter with maximum power point tracking and a voltage source converter is used to control the solar power. The parameters of the VSG-SME are listed in Tables 1–3. VSG 1 SECTION PI COUPLED SECTION PI COUPLED VSG 2 SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED SECTION PI COUPLED Mini HYDRO Mini HYDRO MAIN GRID FIXED LOAD CIRCUIT BREAKER TRANSFORMER LEGEND SOLAR FARM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 16 18 19 20 21 22 VSG 4 VSG 3 VSG 5 VSG 6 Figure 8. The 11 kV 22 bus distribution system. Table 1. Parameters for VSG-SME. Parameters Value SME power 0.95 MW SME storage capacity 0.95 MWh DC link voltage 600 V Line voltage 400 V Inverter switching frequency 2 kHz LCL filter 11 mH, 0.62 µF, 6.6 mH Line reactance, resistance 0.0238 Ohm/km, 0.342 Ohm/km Table 2. Parameters for mini hydro generator. Parameters Value Rated power 1 MVA Rated voltage 11 kV Inertia constant 0.2 s Neutral series resistance 10,000 (pu) Neutral series reactance 0 (pu) Iron loss resistance 300 (pu) Figure 8. The 11 kV 22 bus distribution system Table 1. Parameters for VSG-SME Parameters Value SME power 0.95 MW SME storage capacity 0.95 MWh DC link voltage 600 V Line voltage 400 V Inverter switching frequency 2 kHz LCL filter 11 mH, 0.62 µ F, 6.6 mH Line reactance, resistance 0.0238 Ohm/km, 0.342 Ohm/km

[[[ p. 9 ]]]

[Summary: This page shows the parameters for mini hydro generator and parameters for solar power. It discusses performance assessment through PSCAD/EMTDC using frequency metrics: frequency nadir (FN), frequency spikes, and damping ratio (DR). It compares four VSG controllers.]

Sustainability 2022 , 14 , 10798 9 of 16 Table 2. Parameters for mini hydro generator Parameters Value Rated power 1 MVA Rated voltage 11 kV Inertia constant 0.2 s Neutral series resistance 10,000 (pu) Neutral series reactance 0 (pu) Iron loss resistance 300 (pu) Table 3. Parameters for solar power Parameters Value Number of modules connected in series per array 20 Number of module strings in parallel per array 20 Number of cells connected in series per module 108 Number of cell strings in parallel per module 4 Reference irradiation 1000 W/m 2 Reference cell temperature 25 ◦ C Effective area per cell 0.01 m 2 Series resistance per cell 0.02 Ohm Shunt resistance per cell 1000 Ohm Band gap energy 1.103 eV Saturation current at reference conditions per cell 1 × 10 − 12 kA Short circuit current at reference conditions per cell 0.0025 kA 4. Results and Discussions The performance of the controllers was assessed through PSCAD/EMTDC software The dynamic performance is evaluated using frequency metrics, such as the frequency nadir (FN), frequency spikes, and the damping ratio (DR). The peak-to-peak value for each frequency response should lie within the safe operating frequency of 60 Hz ± 3% Hz [ 14 ]. DR is the measure of the oscillation of a system response. For this simulation, the logarithmic decrement method was used to calculate DR. The best value of DR is known to be 1 √ 2 equals 0.7071, where the response is neither too slow nor too oscillatory [ 15 ]. System response with DR < 0.7071 will generate under damped response. While a system with DR > 0.7071 will generate an overdamped response. Under damped response could cause the system to have a prolonged oscillation and cause instability to the system. Comparisons between 4 VSG controllers were made for all scenarios. The controllers are; (i) NO VSG support (NV), (ii) VSG with a fixed value of J and D (VF), (iii) VSG with fuzzy inference system controller (VFIS), and (iv) VSG with GA-optimized fuzzy inference system controller (VOFIS). The method used for each controller is shown in Table 4 . Table 4. Controller method comparison Controllers Method VSG with fixed value of J and D (VF) The value of J and D is fixed to two constants. Both constants are deduced from a unit pulse interruption response VSG with fuzzy inference system for J and D (VFIS) Value of J and D are scheduled in the form of a fuzzy inference system (FIS). The only input for the FIS is the ROCOF. The uniform triangle membership function is used for the FIS. The range of each MF is fixed VSG with GA-ANFIS for J and D (VOFIS) For the ANFIS, two input MF and two output MFs are set. Change in frequency and ROCOF as the input while constant J and D as the output Both input and output MF are optimized using a genetic algorithm. From the optimization, input and output MF are heuristically designed to manage a wide range of interruptions and responses.

[[[ p. 10 ]]]

[Summary: This page presents the results of Scenario 1, a 100% solar power drop for 0.2s. It analyzes the frequency nadir, recovery time, damping ratio, and frequency spikes for different controllers, concluding that VOFIS performs best.]

Sustainability 2022 , 14 , 10798 10 of 16 4.1. Scenario 1: Solar Drop 100% for 0.2 s For the first scenario, the performance of the system was analyzed by turning off the solar power. At the time, t = 8.16 s, solar power was switched OFF for 0.2 s, and solar was switched back ON at t = 8.36 s to mimic the sudden loss of solar power generation. The first transition at t = 8.16 s created an under-frequency event. The second transition at t = 8.36 s was caused by the sudden reconnection of solar power to the DS and created an over-frequency event. During an under-frequency event, energy stored in the VSG was used to minimize the frequency change. During an over-frequency event, VSG absorbed excess power and charged the energy storage in the VSG The results in the Figures 9 and 10 below show the effect of the sudden switch-off of solar power. Figure 10 is the zoomed-out version of the result in Figure 9 . From figures, FN for VFIS is 59.09 Hz. Whereas the FN for VOFIS is 59.4 Hz. While FN for both VF and NV are well beyond 48 Hz. Although both the FN for VFIS and VOFIS do not differ much, from a frequency recovery point of view, VOFIS has faster recovery at 70 ms compared to VFIS at 90 ms. The damping ratio (DR) value for VOFIS is 0.856 while VFIS 0.1858. From the results, VOFIS is the best DR value and the highest FN At t = 8.36 s, solar power was reconnected and caused an over-frequency event due to the sudden injection of power. VOFIS controller was able to reduce the frequency spike to 60.68 Hz, while the frequency for the VFIS controller spiked up to 62.12 Hz, well beyond the safe frequency operation. During over-frequency events, excess power generated was used to charge the energy storage. It can be concluded that the VOFIS controller was able to absorb more excess power because the controller was optimized to manage a larger range of frequency changes. Besides reducing the peak frequency, VOFIS has the best DR, at 0.8133, as compared to the other controllers in Table 5 . Figures 11 and 12 show the comparison of the J and D value used for the VSG controller. Figures 11 and 12 compare the difference between VFIS and VOFIS fuzzy controller output. As was anticipated, VOFIS has produced a more accurate value for J and D according to the changes in the frequency. VFIS produced an inaccurate value because its MF range was not optimized for the frequency changes Table 5. Frequency nadir, peak, and damping ratio comparison for scenario 1 Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) Frequency Peak, FP (Hz) 2 nd Transition Damping Ratio, DR (%) NV 53.68 <0.01 67.31 3.7169 VF 59.06 0.2536 63.91 5.3174 VFIS 59.09 0.1858 62.12 2.8827 VOFIS 59.40 0.8560 60.68 0.8133 Sustainability 2022 , 14 , x FOR PEER REVIEW 10 of 16 used to minimize the frequency change. During an over-frequency event, VSG absorbed excess power and charged the energy storage in the VSG. The results in the Figures 9 and 10 below show the effect of the sudden switch-off of solar power. Figure 10 is the zoomed-out version of the result in Figure 9. From figures, FN for VFIS is 59.09 Hz. Whereas the FN for VOFIS is 59.4 Hz. While FN for both VF and NV are well beyond 48 Hz. Although both the FN for VFIS and VOFIS do not differ much, from a frequency recovery point of view, VOFIS has faster recovery at 70 ms compared to VFIS at 90 ms. The damping ratio (DR) value for VOFIS is 0.856 while VFIS 0.1858. From the results, VOFIS is the best DR value and the highest FN. At t = 8.36 s, solar power was reconnected and caused an over-frequency event due to the sudden injection of power. VOFIS controller was able to reduce the frequency spike to 60.68 Hz, while the frequency for the VFIS controller spiked up to 62.12 Hz, well beyond the safe frequency operation. During over-frequency events, excess power generated was used to charge the energy storage. It can be concluded that the VOFIS controller was able to absorb more excess power because the controller was optimized to manage a larger range of frequency changes. Besides reducing the peak frequency, VOFIS has the best DR, at 0.8133, as compared to the other controllers in Table 5. Figures 11 and 12 show the comparison of the J and D value used for the VSG controller. Figures 11 and 12 compare the difference between VFIS and VOFIS fuzzy controller output. As was anticipated, VOFIS has produced a more accurate value for J and D according to the changes in the frequency. VFIS produced an inaccurate value because its MF range was not optimized for the frequency changes. Table 5. Frequency nadir, peak, and damping ratio comparison for scenario 1. Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) Frequency Peak, FP (Hz) 2 nd Transition Damping Ratio, DR (%) NV 53.68 <0.01 67.31 3.7169 VF 59.06 0.2536 63.91 5.3174 VFIS 59.09 0.1858 62.12 2.8827 VOFIS 59.40 0.8560 60.68 0.8133 Figure 9. Frequency response comparison for scenario 1. 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 48 50 52 54 56 58 60 62 64 66 Frequency Hz FV NV VOFIS VFIS Figure 9. Frequency response comparison for scenario 1.

[[[ p. 11 ]]]

[Summary: This page shows the zoom out view of the results of Scenario 1. It shows the inertia constant, J, comparison between VFIS and VOFIS and the damping constant, D, comparison between VFIS and VOFIS.]

Sustainability 2022 , 14 , 10798 11 of 16 Sustainability 2022 , 14 , x FOR PEER REVIEW 11 of 16 Figure 10. Zoom out view of Figure 8. Figure 11. Inertia constant, J, comparison between VFIS and VOFIS. Figure 12. Damping constant, D, comparison between VFIS and VOFIS. 4.2. Scenario 2: Solar Variation (Irradiance Change) In this scenario, the transient response of the system was analyzed by varying the solar irradiance after steady state was attained. At a steady state, solar irradiance was maintained at 900 W/m 2 generating 1.32 MW from PV farm. Solar irradiance changes from 8.15 8.2 8.25 8.3 8.35 8.4 8.45 52 54 56 58 60 62 64 66 Frequency Hz FV NV VOFIS VFIS 8 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 -1.5 -1 -0.5 0 0.5 1 1.5 2 2.5 Inertia Constant J VOFIS VFIS VF 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 -150 -100 -50 0 50 100 Damping Constant D VOFIS VFIS VF Figure 10. Zoom out view of Figure 8 . Sustainability 2022 , 14 , x FOR PEER REVIEW 11 of 16 Figure 10. Zoom out view of Figure 8. Figure 11. Inertia constant, J, comparison between VFIS and VOFIS. Figure 12. Damping constant, D, comparison between VFIS and VOFIS. 4.2. Scenario 2: Solar Variation (Irradiance Change) In this scenario, the transient response of the system was analyzed by varying the solar irradiance after steady state was attained. At a steady state, solar irradiance was maintained at 900 W/m 2 generating 1.32 MW from PV farm. Solar irradiance changes from 8.15 8.2 8.25 8.3 8.35 8.4 8.45 52 54 56 58 60 62 64 66 Frequency Hz FV NV VOFIS VFIS 8 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 -1.5 -1 -0.5 0 0.5 1 1.5 2 2.5 Inertia Constant J VOFIS VFIS VF 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 -150 -100 -50 0 50 100 Damping Constant D VOFIS VFIS VF Figure 11. Inertia constant, J , comparison between VFIS and VOFIS Sustainability 2022 , 14 , x FOR PEER REVIEW 11 of 16 Figure 10. Zoom out view of Figure 8. Figure 11. Inertia constant, J, comparison between VFIS and VOFIS. Figure 12. Damping constant, D, comparison between VFIS and VOFIS. 4.2. Scenario 2: Solar Variation (Irradiance Change) In this scenario, the transient response of the system was analyzed by varying the solar irradiance after steady state was attained. At a steady state, solar irradiance was maintained at 900 W/m 2 generating 1.32 MW from PV farm. Solar irradiance changes from 8.15 8.2 8.25 8.3 8.35 8.4 8.45 52 54 56 58 60 62 64 66 Frequency Hz FV NV VOFIS VFIS 8 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 -1.5 -1 -0.5 0 0.5 1 1.5 2 2.5 Inertia Constant J VOFIS VFIS VF 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 -150 -100 -50 0 50 100 Damping Constant D VOFIS VFIS VF Figure 12. Damping constant, D , comparison between VFIS and VOFIS.

[[[ p. 12 ]]]

[Summary: This page discusses Scenario 2: solar irradiance variation. It describes the simulation setup and analyzes the frequency response, damping ratio, and controller performance, highlighting VOFIS's ability to maintain system frequency within safe limits.]

Sustainability 2022 , 14 , 10798 12 of 16 4.2. Scenario 2: Solar Variation (Irradiance Change) In this scenario, the transient response of the system was analyzed by varying the solar irradiance after steady state was attained. At a steady state, solar irradiance was maintained at 900 W/m 2 generating 1.32 MW from PV farm. Solar irradiance changes from 900 W/m 2 to 100 W/m 2 at 8.16 s for 0.2 s while retaining the temperature of the solar panel, which was set at 40 ◦ C. This scenario simulates the intermittent nature of a solar farm. As a result, power generated from PV farm dropped from 1.32 MW to 0.2 MW, subsequently causing an under-frequency event due to power deficit. At t = 8.36 s, the solar irradiance changes from 100 W/m 2 back to 900 W/m 2 . At this point, an over-frequency event occurs due to the sudden injection of solar power Both Figures 13 and 14 shows the frequency response of scenario 2, where Figure 14 is the zoom-out version of Figure 13 . From figures, FN for VOFIS dropped to 59.56 Hz, while for VFIS, the frequency dropped to 59.03 Hz with a high oscillating pattern. VOFIS recovers the frequency faster at 100 ms compared to VFIS at 2 s. From Table 6 , DR for VOFIS and VFIS is 0.5208 and 0.0849. This proved that VFIS produced a high oscillation response compared to VOFIS. Therefore, the transient response for VFIS is longer compared to VOFIS. DR for both VF and NV is lower than 0.01. At t = 8.36 s, VOFIS reduced the over-frequency spikes to only 60.9 Hz compared to VFIS 61.5 Hz. With a VF controller, the frequency spike up to 63 Hz. The ability of the VOFIS controller to absorb excess power and use them to charge the energy storage reduced the frequency spike. Figure 13 shows that frequency recovery using VOFIS is faster and smoother as compared to the other controller. Figure 15 shows the comparison between the value and range of J and D between VOFIS and VFIS. The value of J and D for VOFIS is optimized and fine-tuned according to the changes in the frequency. As a result, VOFIS able to inject and absorb sudden changes in the power hence maintaining the system frequency within the safe operation. Figures 15 and 16 compare the fuzzy output value for VFIS and VOFIS Table 6. Frequency nadir, peak, and damping ratio comparison for scenario 2 Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) Frequency Peak, FP (Hz) 2 nd Transition Damping Ratio, DR (%) NV 58.93 <0.01 63.82 5.606 VF 58.64 <0.01 63.27 4.771 VFIS 59.03 0.0849 61.18 1.853 VOFIS 59.56 0.5208 60.87 1.293 Sustainability 2022 , 14 , x FOR PEER REVIEW 12 of 16 900 W/m 2 to 100 W/m 2 at 8.16 s for 0.2 s while retaining the temperature of the solar panel, which was set at 40 °C. This scenario simulates the intermittent nature of a solar farm. As a result, power generated from PV farm dropped from 1.32 MW to 0.2 MW, subsequently causing an under-frequency event due to power deficit. At t = 8.36 s, the solar irradiance changes from 100 W/m 2 back to 900 W/m 2 . At this point, an over-frequency event occurs due to the sudden injection of solar power. Both Figures 13 and 14 shows the frequency response of scenario 2, where Figure 14 is the zoom-out version of Figure 13. From figures, FN for VOFIS dropped to 59.56 Hz, while for VFIS, the frequency dropped to 59.03 Hz with a high oscillating pattern. VOFIS recovers the frequency faster at 100 ms compared to VFIS at 2 s. From Table 6, DR for VOFIS and VFIS is 0.5208 and 0.0849. This proved that VFIS produced a high oscillation response compared to VOFIS. Therefore, the transient response for VFIS is longer compared to VOFIS. DR for both VF and NV is lower than 0.01. At t = 8.36 s, VOFIS reduced the over-frequency spikes to only 60.9 Hz compared to VFIS 61.5 Hz. With a VF controller, the frequency spike up to 63 Hz. The ability of the VOFIS controller to absorb excess power and use them to charge the energy storage reduced the frequency spike. Figure 13 shows that frequency recovery using VOFIS is faster and smoother as compared to the other controller. Figure 15 shows the comparison between the value and range of J and D between VOFIS and VFIS. The value of J and D for VOFIS is optimized and fine-tuned according to the changes in the frequency. As a result, VOFIS able to inject and absorb sudden changes in the power hence maintaining the system frequency within the safe operation. Figures 15 and 16 compare the fuzzy output value for VFIS and VOFIS. Table 6. Frequency nadir, peak, and damping ratio comparison for scenario 2. Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) Frequency Peak, FP (Hz) 2 nd Transition Damping Ratio, DR (%) NV 58.93 <0.01 63.82 5.606 VF 58.64 <0.01 63.27 4.771 VFIS 59.03 0.0849 61.18 1.853 VOFIS 59.56 0.5208 60.87 1.293 Figure 13. Frequency response comparison for scenario 2. 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 58.5 59 59.5 60 60.5 61 61.5 62 62.5 63 63.5 Frequency Hz VF VFIS VOFIS NV Figure 13. Frequency response comparison for scenario 2.

[[[ p. 13 ]]]

[Summary: This page shows the zoomed out view of the results of Scenario 2. It shows the damping constant, D, comparison between VFIS and VOFIS and the inertia constant, J, comparison between VFIS and VOFIS.]

Sustainability 2022 , 14 , 10798 13 of 16 Sustainability 2022 , 14 , x FOR PEER REVIEW 13 of 16 Figure 14. Zoomed out view of Figure 12. Figure 15. Damping constant, D, comparison between VFIS and VOFIS. Figure 16. Inertia constant, J, comparison between VFIS and VOFIS. 4.3. Scenario 3: Islanding Event In this scenario, DS was islanded at time t = 8.16 s by opening the main grid circuit breaker. Figure 17 shows that VOFIS can reach stability without overshooting beyond safe frequency operation. VFIS, on the other hand, could not react to the islanding event. This 8.15 8.2 8.25 8.3 8.35 8.4 58.5 59 59.5 60 60.5 61 61.5 Frequency Hz VF VFIS VOFIS NV 8.2 8.4 8.6 8.8 9 9.2 -40 -30 -20 -10 0 10 20 30 40 Damping Constant D VFIS VOFIS VF 8.2 8.4 8.6 8.8 9 9.2 9.4 -1.2 -1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 Inertia Constant J VFIS VOFIS VF Figure 14. Zoomed out view of Figure 12 . Sustainability 2022 , 14 , x FOR PEER REVIEW 13 of 16 Figure 14. Zoomed out view of Figure 12. Figure 15. Damping constant, D, comparison between VFIS and VOFIS. Figure 16. Inertia constant, J, comparison between VFIS and VOFIS. 4.3. Scenario 3: Islanding Event In this scenario, DS was islanded at time t = 8.16 s by opening the main grid circuit breaker. Figure 17 shows that VOFIS can reach stability without overshooting beyond safe frequency operation. VFIS, on the other hand, could not react to the islanding event. This 8.15 8.2 8.25 8.3 8.35 8.4 58.5 59 59.5 60 60.5 61 61.5 Frequency Hz VF VFIS VOFIS NV 8.2 8.4 8.6 8.8 9 9.2 -40 -30 -20 -10 0 10 20 30 40 Damping Constant D VFIS VOFIS VF 8.2 8.4 8.6 8.8 9 9.2 9.4 -1.2 -1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 Inertia Constant J VFIS VOFIS VF Figure 15. Damping constant, D , comparison between VFIS and VOFIS Sustainability 2022 , 14 , x FOR PEER REVIEW 13 of 16 Figure 14. Zoomed out view of Figure 12. Figure 15. Damping constant, D, comparison between VFIS and VOFIS. Figure 16. Inertia constant, J, comparison between VFIS and VOFIS. 4.3. Scenario 3: Islanding Event In this scenario, DS was islanded at time t = 8.16 s by opening the main grid circuit breaker. Figure 17 shows that VOFIS can reach stability without overshooting beyond safe frequency operation. VFIS, on the other hand, could not react to the islanding event. This 8.15 8.2 8.25 8.3 8.35 8.4 58.5 59 59.5 60 60.5 61 61.5 Frequency Hz VF VFIS VOFIS NV 8.2 8.4 8.6 8.8 9 9.2 -40 -30 -20 -10 0 10 20 30 40 Damping Constant D VFIS VOFIS VF 8.2 8.4 8.6 8.8 9 9.2 9.4 -1.2 -1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 Inertia Constant J VFIS VOFIS VF Figure 16. Inertia constant, J , comparison between VFIS and VOFIS 4.3. Scenario 3: Islanding Event In this scenario, DS was islanded at time t = 8.16 s by opening the main grid circuit breaker. Figure 17 shows that VOFIS can reach stability without overshooting beyond safe frequency operation. VFIS, on the other hand, could not react to the islanding event. This

[[[ p. 14 ]]]

[Summary: This page analyzes Scenario 3: an islanding event. It compares the performance of VOFIS and VFIS controllers during islanding, noting VOFIS's ability to reduce frequency changes while VFIS struggles. It shows frequency nadir, peak, and damping ratio comparison.]

Sustainability 2022 , 14 , 10798 14 of 16 could be seen from the value of J and D in Figures 18 and 19 . The controller was unable to produce a new variation of J and D as the frequency detected is out of the input MF range. Both J and D were set to zero during the islanding process. On the other hand, VOFIS reacted and reduced the frequency changes during the inertial phase. The FN for VOFIS dropped to 59.44 Hz while 48.87 Hz for VFIS. As shown in Table 7 , the DR for VFIS is overdamped at 9.163, while DR for VOFIS is underdamped at 0.203. Even though the DR for VOFIS is underdamped, the response time for the frequency to stable. VOFIS recovers 7 s after islanding while VFIS 9 s after Table 7. Frequency nadir, peak, and damping ratio comparison for scenario 3 Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) VFIS 48.87 9.163 VOFIS 59.44 0.203 Sustainability 2022 , 14 , x FOR PEER REVIEW 14 of 16 could be seen from the value of J and D in Figures 18 and 19. The controller was unable to produce a new variation of J and D as the frequency detected is out of the input MF range. Both J and D were set to zero during the islanding process. On the other hand, VOFIS reacted and reduced the frequency changes during the inertial phase. The FN for VOFIS dropped to 59.44 Hz while 48.87 Hz for VFIS. As shown in Table 7, the DR for VFIS is overdamped at 9.163, while DR for VOFIS is underdamped at 0.203. Even though the DR for VOFIS is underdamped, the response time for the frequency to stable. VOFIS recovers 7 s after islanding while VFIS 9 s after. Table 7. Frequency nadir, peak, and damping ratio comparison for scenario 3. Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) VFIS 48.87 9.163 VOFIS 59.44 0.203 Figure 17. Frequency response comparison for scenario 3. Figure 18. Inertia constant, J, comparison between VFIS and VOFIS. 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 59 59.2 59.4 59.6 59.8 60 60.2 60.4 60.6 Frequency Hz VOFIS VFIS 8 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 -1 -0.5 0 0.5 1 1.5 2 2.5 3 Inertia Constant J VOFIS VFIS Figure 17. Frequency response comparison for scenario 3 Sustainability 2022 , 14 , x FOR PEER REVIEW 14 of 16 could be seen from the value of J and D in Figures 18 and 19. The controller was unable to produce a new variation of J and D as the frequency detected is out of the input MF range. Both J and D were set to zero during the islanding process. On the other hand, VOFIS reacted and reduced the frequency changes during the inertial phase. The FN for VOFIS dropped to 59.44 Hz while 48.87 Hz for VFIS. As shown in Table 7, the DR for VFIS is overdamped at 9.163, while DR for VOFIS is underdamped at 0.203. Even though the DR for VOFIS is underdamped, the response time for the frequency to stable. VOFIS recovers 7 s after islanding while VFIS 9 s after. Table 7. Frequency nadir, peak, and damping ratio comparison for scenario 3. Controller Strategies Frequency Nadir, FN (Hz) 1 st Transition Damping Ratio, DR (%) VFIS 48.87 9.163 VOFIS 59.44 0.203 Figure 17. Frequency response comparison for scenario 3. Figure 18. Inertia constant, J, comparison between VFIS and VOFIS. 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 9 59 59.2 59.4 59.6 59.8 60 60.2 60.4 60.6 Frequency Hz VOFIS VFIS 8 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 -1 -0.5 0 0.5 1 1.5 2 2.5 3 Inertia Constant J VOFIS VFIS Figure 18. Inertia constant, J , comparison between VFIS and VOFIS.

[[[ p. 15 ]]]

[Summary: This page shows the damping constant, D, comparison between VFIS and VOFIS. It concludes that the proposed GA-ANFIS-based VSG controller improves VSG performance, maintaining frequency within safe limits with better transient response and faster recovery.]

Sustainability 2022 , 14 , 10798 15 of 16 Sustainability 2022 , 14 , x FOR PEER REVIEW 15 of 16 Figure 19. Damping constant, D, comparison between VFIS and VOFIS. 5. Conclusions In this paper, a new active power controller for VSG has been developed based on ANFIS, in which membership functions are optimized using GA. The values of inertia constant, J, and damping constant, D, in a VSG controller are controlled through the proposed controller to ensure the improved operation of the VSG controller. Through the simulations conducted in the PSCAD platform on an 11 kV Malaysian practical distribution system for various cases, it has been proved that the proposed ANFIS-GA-based controller has improved the performance of the VSG compared to the conventional VSG controller. From the simulation results, it has been observed that the proposed controller managed to maintain the DS frequency within the safe operating limit of 60 ± 1.8 Hz, better transient response, and faster recovery time during all the three cases (100% solar drop, solar irradiation changes, and islanding event). VOFIS able to recover the frequency 22% faster compared to the other controllers. From the analysis of the above results, it can be concluded that the values of J and D for the proposed VOFIS are optimized and fine-tuned according to the changes in the frequency. As a result, VOFIS able to inject and absorb sudden changes in the power hence maintaining the system frequency within the safe operation. This paper serves as an initial work for coordinating multiple energy storage systems in VSG as an ancillary service to the DS. Furthermore, different types of metaheuristic optimization should be implemented and compared to obtain the best method for VSG application. Optimization of J and D constants in the VSG controller plays a vital role in regulating the VSG power output to maintain stable frequency operation during islanded DS operation. Without the help from VSG as an ancillary service, DS could not maintain the frequency in the safe operating region, which may result in the malfunction of DS. Therefore, it can be said that through the implementation of the proposed optimized GA-ANFIS-based VSG controller, the sustainable and reliable operation of DS has been ensured. Author Contributions: Conceptualization, M.H.O. and H.M. (Hazlie Mokhlis); methodology, M.H.O. and H.M. (Hazlie Mokhlis); software, M.H.O. and H.M. (Hazlie Mokhlis); validation, H.M. (Hazlie Mokhlis), M.M., and N.F.A.A.; formal analysis, N.N.M., S.A., and N.F.A.A.; investigation, M.H.O. and H.M. (Hazlie Mokhlis); resources, H.M. (Hazlie Mokhlis), M.M., and N.F.A.A.; data curation, M.H.O. and H.M. (Hazlie Mokhlis); writing—original draft preparation, M.H.O.; writing—review and editing, H.M. (Hazlie Mokhlis), M.M., and S.A.; visualization, M.H.O.; supervision, H.M. (Hazlie Mokhlis), M.M. and N.F.A.A.; project administration, H.M. (Hasmaini Mohamad); funding acquisition, H.M. (Hasmaini Mohamad) and H.M. (Hazlie Mokhlis). All authors have read and agreed to the published version of the manuscript. 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 -200 -150 -100 -50 0 50 100 Damping Constant D VOFIS VFIS Figure 19. Damping constant, D , comparison between VFIS and VOFIS 5. Conclusions In this paper, a new active power controller for VSG has been developed based on ANFIS, in which membership functions are optimized using GA. The values of inertia constant, J , and damping constant, D , in a VSG controller are controlled through the proposed controller to ensure the improved operation of the VSG controller. Through the simulations conducted in the PSCAD platform on an 11 kV Malaysian practical distribution system for various cases, it has been proved that the proposed ANFIS-GA-based controller has improved the performance of the VSG compared to the conventional VSG controller From the simulation results, it has been observed that the proposed controller managed to maintain the DS frequency within the safe operating limit of 60 ± 1.8 Hz, better transient response, and faster recovery time during all the three cases (100% solar drop, solar irradiation changes, and islanding event). VOFIS able to recover the frequency 22% faster compared to the other controllers From the analysis of the above results, it can be concluded that the values of J and D for the proposed VOFIS are optimized and fine-tuned according to the changes in the frequency. As a result, VOFIS able to inject and absorb sudden changes in the power hence maintaining the system frequency within the safe operation. This paper serves as an initial work for coordinating multiple energy storage systems in VSG as an ancillary service to the DS. Furthermore, different types of metaheuristic optimization should be implemented and compared to obtain the best method for VSG application. Optimization of J and D constants in the VSG controller plays a vital role in regulating the VSG power output to maintain stable frequency operation during islanded DS operation. Without the help from VSG as an ancillary service, DS could not maintain the frequency in the safe operating region, which may result in the malfunction of DS. Therefore, it can be said that through the implementation of the proposed optimized GA-ANFIS-based VSG controller, the sustainable and reliable operation of DS has been ensured Author Contributions: Conceptualization, M.H.O. and H.M. (Hazlie Mokhlis); methodology, M.H.O and H.M. (Hazlie Mokhlis); software, M.H.O. and H.M. (Hazlie Mokhlis); validation, H.M. (Hazlie Mokhlis), M.M., and N.F.A.A.; formal analysis, N.N.M., S.A., and N.F.A.A.; investigation, M.H.O. and H.M. (Hazlie Mokhlis); resources, H.M. (Hazlie Mokhlis), M.M., and N.F.A.A.; data curation, M.H.O. and H.M. (Hazlie Mokhlis); writing—original draft preparation, M.H.O.; writing—review and editing, H.M. (Hazlie Mokhlis), M.M., and S.A.; visualization, M.H.O.; supervision, H.M. (Hazlie Mokhlis), M.M. and N.F.A.A.; project administration, H.M. (Hasmaini Mohamad); funding acquisition, H.M (Hasmaini Mohamad) and H.M. (Hazlie Mokhlis). All authors have read and agreed to the published version of the manuscript.

[[[ p. 16 ]]]

[Summary: This page acknowledges funding sources and declares no conflicts of interest. It provides a list of references used in the paper.]

Sustainability 2022 , 14 , 10798 16 of 16 Funding: This research is supported by the Ministry of Higher Education, Malaysiaunder Fundamental Research Grant Scheme (FRGS/1/2019/TK 04/UM/01/1) and Universiti Malaya underthe Impact-Oriented Interdisciplinary Research Grant (IIRG 001 A-2020 IISS) Institutional Review Board Statement: Not applicable Informed Consent Statement: Not applicable Data Availability Statement: Not applicable Conflicts of Interest: The authors declare no conflict of interest References 1 Energy Sector Management Assistance Program Public Disclosure Authorized Annual Report 2021 Energy Sector Management ; World Bank: Washington, DC, USA, 2021; ISBN 1202522262 2 SEDA Malaysia. Malaysia Renewable Energy Roadmap: Pathway towards Low Carbon Energy. 2021. Available online: www.seda.gov.my (accessed on 10 January 2022) 3 Ratnam, K.S.; Palanisamy, K.; Yang, G. Future low-inertia power systems: Requirements, issues, and solutions—A review Renew Sustain. Energy Rev 2020 , 124 , 109773. [ CrossRef ] 4 Ackermann, T.; Andersson, G.; Söder, L. Distributed generation: A definition Electr. Power Syst. Res 2001 , 57 , 195–204. [ CrossRef ] 5 Othman, M.H.; Mokhlis, H.; Mubin, M.; Talpur, S.; Ab Aziz, N.F.; Dradi, M.; Mohamad, H. Progress in control and coordination of energy storage system-based VSG: A review IET Renew. Power Gener 2020 , 14 , 177–187. [ CrossRef ] 6 Liang, X.; Karim, C.A. Virtual synchronous machine method in renewable energy integration. In Proceedings of the 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conference, Xi’an, China, 25–28 October 2016; pp. 364–368 7 Alipoor, J.; Miura, Y.; Ise, T. Voltage sag ride-through performance of virtual synchronous generator. In Proceedings of the 2014 International Power Electronics Conference (IPEC-Hiroshima 2014—ECCE ASIA), Hiroshima, Japan, 18–21 May 2014; pp. 3298–3305 8 Wang, F.; Zhang, L.; Feng, X.; Guo, H. An Adaptive Control Strategy for Virtual IEEE Trans. Ind. Appl 2018 , 54 , 5124–5133 [ CrossRef ] 9 Mentesidi, K.; Garde, R.; Aguado, M.; Rikos, E. Implementation of a fuzzy logic controller for virtual inertia emulation. In Proceedings of the 2015 International Symposium on Smart Electric Distribution Systems and Technologies, Vienna, Austria, 7–11 September 2015; pp. 606–611 10 Esfahani, M.M.; Habib, H.F.; Mohammed, O.A. Microgrid stability improvement using a fuzzy-based PSS design for virtual synchronous generator. In Proceedings of the SoutheastCon 2018, St. Petersburg, FL, USA, 19–22 April 2018; pp. 1–5 11 Andalib-Bin-Karim, C.; Liang, X.; Zhang, H. Fuzzy secondary controller based virtual synchronous generator control scheme for interfacing inverters of renewable distributed generation in microgrids IEEE Trans. Ind. Appl 2018 , 54 , 1047–1061. [ CrossRef ] 12 Yang, X.-S. Genetic Algorithms. In Nature Inspired Optimization Algorithms , 1 st ed.; Elsevier: Amsterdam, The Netherlands, 2014; pp. 91–100, ISBN 978-0-12-416743-8 13 Karaboga, D.; Kaya, E. Adaptive network based fuzzy inference system (ANFIS) training approaches: A comprehensive survey Artif. Intell. Rev 2019 , 52 , 2263–2293. [ CrossRef ] 14 Suruhanjaya Tenaga Grid Code For Peninsular Malaysia (Amendments) 2020. 2020; p. 453. Available online: https://www.st.gov. my/ (accessed on 3 May 2022) 15 Evans, W.R Control-System Dynamics , 1 st ed.; McGraw-Hill Book Company: New York, NY, USA, 1954; ISBN 1124088059.

Other Environmental Sciences Concepts:

[back to top]

Discover the significance of concepts within the article: ‘Genetic Algorithm-Optimized Adaptive Network Fuzzy Inference System-Based VSG...’. Further sources in the context of Environmental Sciences might help you critically compare this page with similair documents:

Ga, Shme, Inertia, Active power, Number of cells, Steady state, Recovery time, Training set, Band gap energy, Response time, Greenhouse Gases, Fuzzy Inference System, Distribution system, Solar Power, Frequency, Power generation, Energy storage, Objective Function, Sustainable operation, Energy Storage System, Short circuit current, Oscillation, Sustainable, Testing set, Genetic algorithm, Solar irradiance, Power System, Renewable Energy Source, ANFIS, Membership function, Non-renewable energy source, Transient Response, Ancillary Service, Input Membership Function, Output Membership Function, Dynamic performance, Real-time scheduling, Transient simulation, Number of modules, Solar variation, Solar panel, System response, Fixed value, Metaheuristic Optimization, Faster Recovery Time.

Let's grow together!

I humbly request your help to keep doing what I do best: provide the world with unbiased sources, definitions and images. Your donation direclty influences the quality and quantity of knowledge, wisdom and spiritual insight the world is exposed to.

Let's make the world a better place together!

Like what you read? Help to become even better: